EIT Tables 5-8, 5-43 to 5-46

Correction Factors

Multiply the tabulated ampacity by every factor that applies: Iz = It · Ca · Cg. Air tables are based on 40 °C ambient; underground tables on 30 °C ground.

Table 5-43 — Ambient temperature in air (base 40 °C)
Ambient (°C)PVCXLPE / EPR
11–151.341.23
16–201.291.19
21–251.221.14
26–301.151.10
31–351.081.05
36–401.001.00
41–450.910.96
46–500.820.90
51–550.700.84
56–600.570.78
61–65–0.71
66–70–0.64
71–75–0.55
76–80–0.45
Table 5-44 — Ground temperature (base 30 °C)
Ground (°C)PVCXLPE / EPR
11–151.181.12
16–201.121.08
21–251.071.03
26–301.001.00
31–350.940.96
36–400.870.91
41–450.800.86
46–500.710.82
51–550.620.76
56–600.510.70
61–65–0.65
66–70–0.57
71–75–0.49
76–80–0.41
Table 5-8 — Circuits in one raceway
CircuitsFactor
11.00
20.80
30.70
40.65
50.60
60.57
70.54
80.52
90.50
10–120.45
13–160.41
17–200.38
Table 5-45 — Direct-buried circuits side by side
CircuitsTouchingOne diameter125 mm250 mm500 mm
20.750.800.850.900.90
30.650.700.750.800.85
40.600.600.700.750.80
50.550.550.650.700.80
60.500.550.600.700.80
Table 5-46 — Buried conduits side by side
ConduitsTouching250 mm500 mm1000 mm
20.850.900.950.95
30.750.850.900.95
40.700.800.850.90
50.650.800.850.90
60.600.800.800.90

Cable tray grouping (Tables 5-40 and 5-41) depends on tray type, arrangement and the number of trays — the Cable Sizing calculator applies it for group 7.

Source: EIT 2001-56 Tables 5-8, 5-43, 5-44, 5-45 and 5-46. Verify against the edition that governs your project before design use.