EIT Tables 5-20 to 5-33

Cable Ampacity

Tabulated current-carrying capacity of low-voltage copper cables for each EIT installation group. Values are before correction for ambient temperature and grouping.

EIT Table 5-20 — Conduit in air (groups 1 & 2)(70 °C conductor, 40 °C ambient; amperes)
Size (mm²)G1 · 2c singleG1 · 2c multiG1 · 3c singleG1 · 3c multiG2 · 2c singleG2 · 2c multiG2 · 3c singleG2 · 3c multi
110109912111010
1.51312121115141313
2.51716161521201817
42322212028262423
63028272536333130
104037373450454440
165350494566605954
257065645988787770
3586807772109979686
50104969486131116117103
70131121118109167146149130
95158145143131202175180156
120183167164150234202208179
150209191188171261224228196
185238216213194297256258222
240279253249227348299301258
300319291285259398343343295
400––––475–406–
500––––545–464–

Apply the ambient and grouping factors from Correction Factors, or let the Cable Sizing calculator do it for you.

Source: EIT 2001-56 (Thai Electrical Code 2013) Tables 5-20 to 5-33. Verify against the edition that governs your project before design use.