Voltage Drop Calculator
Single- and three-phase feeder voltage drop with conductor resistance at operating temperature, reactance and power factor — plus the smallest size that meets your limit.
1
Circuit
Supply and load
Supply
Line-line
2
Cable
Conductor and route
Conductor
70 PVC, 90 XLPE
EIT 3.6: 5 % total
3
Calculation Results
Voltage drop
2.62
%
OK ≤ 3 %
Voltage drop
10.49
V
Receiving end
389.5
V
Minimum Cu size within 3 %: 16 mm² (2.62 %).
Calculation BreakdownFactors, formula and table lookups
- Factor b
- √3
- R at 70 °C
- 1.3760 Ω/km
- X
- 0.08 Ω/km
- cos φ / sin φ
- 0.85 / 0.5268
- ΔV
- 10.49 V
Code Reference
Standards this calculation is based on
- IEC 60364-5-52
Annex G — ΔV = b·I·L·(R cosφ + X sinφ)
- IEC 60228
Class 2 conductor resistance at 20 °C, corrected to temperature
Always verify against the standard edition and utility requirements that apply to your project before issuing for construction.