Back to Elec Data
EIT Table 5-48

Cable Types (TIS 11-2553)

PVC-insulated copper cables to TIS 11-2553 and where the Thai Electrical Code allows each one to be installed. Note the burial rule: only sheathed NYY, NYY-G and VCT may go in buried conduit or direct burial.

Cable codeSizes (mm²)ConductorCoresMax tempSheathUo/U (V)Permitted use
60227 IEC 01THW1.5–400Solid or strandedSingle70 °CNo450/750
  • General use
  • In raceways, protected from water entering the raceway
  • Not in buried conduit or direct burial
60227 IEC 021.5–240FlexibleSingle70 °CNo450/750
  • General use
  • In raceways, protected from water entering the raceway
  • Not in buried conduit or direct burial
60227 IEC 050.5–1.0SolidSingle70 °CNo300/500
  • General use
  • In raceways, protected from water entering the raceway
  • Not in buried conduit or direct burial
60227 IEC 060.5–1.0FlexibleSingle70 °CNo300/500
  • General use
  • In raceways, protected from water entering the raceway
  • Not in buried conduit or direct burial
60227 IEC 070.5–2.5SolidSingle90 °CNo300/500
  • General use
  • In raceways, protected from water entering the raceway
  • Not in buried conduit or direct burial
60227 IEC 080.5–2.5FlexibleSingle90 °CNo300/500
  • General use
  • In raceways, protected from water entering the raceway
  • Not in buried conduit or direct burial
60227 IEC 101.5–35StrandedMulti (with/without earth)70 °CYes300/500
  • General use
  • In raceways, protected from water entering the raceway
  • On cable tray
  • Not in buried conduit or direct burial
60227 IEC 410.8Stranded270 °CNo300/300
  • Inside electronic equipment
60227 IEC 430.5–0.75Flexible170 °CYes300/300
  • Decorative lighting inside buildings
60227 IEC 520.5–0.75FlexibleMulti (with/without earth)70 °CYes300/300
  • Cords for portable appliances
  • Internal wiring of appliances
60227 IEC 530.75–2.5FlexibleMulti (with/without earth)70 °CYes300/500
  • Cords for portable appliances (heavy duty)
  • Connections to luminaires
60227 IEC 560.5–0.75FlexibleMulti (with/without earth)90 °CYes300/300
  • Cords for portable appliances (heavy duty)
60227 IEC 570.75–2.5FlexibleMulti (with/without earth)90 °CYes300/500
  • Cords for portable appliances (heavy duty)
  • Luminaires with or without ballast
  • Advertising and illuminated signs
NYY1–500 single-core; 50–300 multi-coreStrandedSingle or multi70 °CYes450/750
  • General use
  • On cable tray
  • In buried conduit or direct burial
NYY-G25–300StrandedMulti with earth70 °CYes450/750
  • General use
  • On cable tray
  • In buried conduit or direct burial
VAF / VAF-G1–16Solid or stranded2, or 2 with earth70 °CYes300/500
  • Clipped direct to walls
  • In raceways but not in conduit
  • Not buried
VCT / VCT-G4–35FlexibleSingle, multi, multi with earth70 °CYes450/750
  • General use
  • Connections to appliances
  • On cable tray
  • In buried conduit or direct burial

Source: EIT 2001-56 Table 5-48, usage requirements of PVC-insulated copper cables to TIS 11-2553. Verify against the edition that governs your project before design use.