IEC 60228

Conductor Resistance

Maximum DC resistance of class 2 (stranded) conductors at 20 °C, and the value at your operating temperature using R = R20 · (1 + α (t − 20)). These are the values the Voltage Drop and Cable Sizing calculators use.

70 °C PVC, 90 °C XLPE

Size (mm²)Cu R20 (Ω/km)Cu R70 (Ω/km)Al R20 (Ω/km)Al R70 (Ω/km)
1.512.100014.4776––
2.57.41008.8661––
44.61005.5159––
63.08003.6852––
101.83002.1896––
161.15001.37601.91002.2949
250.72700.86991.20001.4418
350.52400.62700.86801.0429
500.38700.46300.64100.7702
700.26800.32070.44300.5323
950.19300.23090.32000.3845
1200.15300.18310.25300.3040
1500.12400.14840.20600.2475
1850.09910.11860.16400.1970
2400.07540.09020.12500.1502
3000.06010.07190.10000.1202
4000.04700.0562––
5000.03660.0438––

Source: IEC 60228 class 2 maximum DC resistance at 20 °C; α = 0.00393 /K (Cu), 0.00403 /K (Al). Verify against the edition that governs your project before design use.