Cable Sizing Calculator
Copper PVC / XLPE cables per the Thai Electrical Code EIT 2001-56 (วสท. 2556), installation groups 1–7: conduit, clipped direct, insulators, buried and cable tray.
1
Load & Cable
Design current and cable construction
Load
Cable
2
Installation
Method, ambient temperature and grouping (EIT Table 5-47)
Method
Grouping
Table 5-8
3
Voltage Drop Check
Upsize automatically when the drop exceeds the limit
Line-line
EIT 3.6: 5 % total
4
Calculation Results
Cable size
50
mm²
Cu PVC
Corrected Iz
117.0
A
Loading Ib / Iz
85
%
Voltage drop
0.94
%
Governed by current-carrying capacity.
EIT 3.6 limits the total drop from the meter to the last outlet to 5 %; this check covers this run only.
Size the breaker for this cable →Calculation BreakdownFactors, formula and table lookups
- Ambient factor Ca
- 1.00
- Grouping factor Cg
- 1.00
- Required It = Ib / (Ca·Cg)
- 100.0 A
- Tabulated It, Table 5-20
- 117 A
- Corrected Iz = It·Ca·Cg
- 117.0 A
- Size by ampacity alone
- 50 mm²
- Conductor resistance
- 0.4630 Ω/km @ 70 °C
- Voltage drop
- 3.77 V
Code Reference
Standards this calculation is based on
- EIT 2001-562556
Ampacity Table 5-20
- EIT 2001-562556
Ambient Table 5-43; grouping Table 5-8
- IEC 60364-5-52
Annex G voltage drop; IEC 60228 resistance
Always verify against the standard edition and utility requirements that apply to your project before issuing for construction.