Back to Library
CablesEIT 2001-56 · Chapter 5

Cable Sizing Calculator

Copper PVC / XLPE cables per the Thai Electrical Code EIT 2001-56 (วสท. 2556), installation groups 1–7: conduit, clipped direct, insulators, buried and cable tray.

1

Load & Cable

Design current and cable construction

Load

Cable

2

Installation

Method, ambient temperature and grouping (EIT Table 5-47)

Method

Grouping

Table 5-8

3

Voltage Drop Check

Upsize automatically when the drop exceeds the limit

Line-line

EIT 3.6: 5 % total

4

Calculation Results

Cable size
50
mm²
Cu PVC
Corrected Iz
117.0
A
Loading Ib / Iz
85
%
Voltage drop
0.94
%

Governed by current-carrying capacity.

EIT 3.6 limits the total drop from the meter to the last outlet to 5 %; this check covers this run only.
Size the breaker for this cable →
Calculation BreakdownFactors, formula and table lookups
Ambient factor Ca
1.00
Grouping factor Cg
1.00
Required It = Ib / (Ca·Cg)
100.0 A
Tabulated It, Table 5-20
117 A
Corrected Iz = It·Ca·Cg
117.0 A
Size by ampacity alone
50 mm²
Conductor resistance
0.4630 Ω/km @ 70 °C
Voltage drop
3.77 V

Code Reference

Standards this calculation is based on

  • EIT 2001-562556

    Ampacity Table 5-20

  • EIT 2001-562556

    Ambient Table 5-43; grouping Table 5-8

  • IEC 60364-5-52

    Annex G voltage drop; IEC 60228 resistance

Always verify against the standard edition and utility requirements that apply to your project before issuing for construction.